Rule 901:5-3-05 | Location of containers.
(A) Consideration shall be given to the physiological effects of ammonia as well as to adjacent fire hazards in selecting the location for a storage container. Containers shall be located outside of any building or in a building or section thereof especially approved for this purpose;
(B) Containers shall be located at least fifty feet from a dug well or other sources of potable water supply;
(C) The location of permanent storage containers shall be outside densely populated areas;
(D) Container locations shall comply with the following table:
Minimum distances (feet) from Container to: | |||
Nominal Capacity of Container (Gallons) | Line of Adjoining Property which may be built upon, Highways & Mainline of Railroad | Place of Public Assembly | Institution Occupancy |
Over 500 to 2,000 | 25 | 150 | 200 |
Over 2,000 to 30,000 | 50 | 300 | 500 |
Over 30,000 to 100,000 | 50 | 450 | 750 |
Over 100,000 | 50 | 600 | 1,000 |
(E) Storage areas shall be kept free at all times of readily ignitable materials such as, but not limited to, waste, weeds and long dry grass.